Here is what you may need to know:

  • Both are deemed to control the dryer cooling capacity as per the requirement/ loading of the dryer.
  • Both function using their probe to check the refrigerant temp upstream the compressor/downstream evaporator to adjust the refrigerant flow and cooling capacity.
  • Both are filled with a gas which could be identical to the dryer refrigerant or different.
  • Both convert the temp into pressure to accomplish the refrigerant flow control and thereon the dryer cooling capacity.
  • Both are adjustable.
  • While TXV controls the dryer capacity by adjusting the liquid refrigerant entering the evaporator, HGBPV adjusts the high temp., high pressure gaseous refrigerant return back to the compressor.
  • While for reduced loading of the dryer, TXV limits the refrigerant flow into the evaporator, HGBPV, directs more refrigerant gas back into the compressor.
  • While TXV is the first to react to partial loading, HGBPV starts later to prevent TXV from overcompensating.